| Plan Review Notes For Permit 02100711 |
| Permit Number |
02100711 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-05 00:00:00 | PROVISO:TYPE III | | | 1.PLAN SHEET AC-D1 GE WASHER/DRYER | | | MODEL SPECIFICATIONS, SPECS INDICATE | | | ELECTRIC & GAS DRYERS, SHOULD GAS DRYERS | | | BE INSTALLED CALCULATIONS FOR COMBUSTION | | | AIR WILL BE REQUIRED. | | | | | | 2.PLAN SHEET AC-D2 DETAIL FOR TOILET | | | EXHAUST, AS PER 2001 FBC(M) 607.4, | | | DUCTS EXTENDING THROUGH MORE THAN ONE | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE HAVING A FIRE RESISTANCE | | | RATING OF 1HR FOR BUILDINGS LESS THAN | | | 4 STORIES & 2HR FOR BUILDINGS GREATER | | | THAN 4 STORIES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|