Plan Review Notes
Plan Review Notes For Permit 02100711
Permit Number 02100711
Review Stop M
Sequence Number 1
Notes
Date Text
2002-11-05 00:00:00DENIED:TYPE III
  
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.NOTES CONCERNING THE DRYER & TOILET
 EXHAUST ARE NOT CLEAR.PLAN SHEET
 AC-U3 NOTE INDICATES SHAFT TO START
 AT THE 2ND FLOOR AT THE ELECTRICAL
 CLOSET?DETIAL ON PLAN SHEET AC-D1
 INDICATES A 1 HR CAULK. PLAN
 SHEET A-DT1 SHOWS A 1 HR SHAFT
 DETAIL FOR THE TOILET & DRYER
 EXHAUST.
  
 PLEASE PROVIDE A RISER DETAIL
 SHOWING WHERE THE SHAFT BEGINS &
 ENDS.REFERENCE PLAN SHEET A-DT1,
 (SHAFT DETAIL) ON THE MECHANICAL
 PLAN.
  
 2.PLAN SHEET AC-D1 - NOTE #2 STATES,
 DRYER EXHASUT DISCHARGE ON ROOF
 SHALL BE SIMILAR TO TOILET EXHAUST
 DISCHARGE BUT SHALL NOT BE SCREENED.
 AS PER 2001 FBC(M) 504.4, SHALL
 TERMINATE ON THE OUTSIDE OF THE
 BUILDING & SHALL BE EQUIPPED WITH A
 BACKDRAFT DAMPER.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) 402.2
 FOR NATURAL VENTILATION OR TABLE
 403.3.PROVIDE CALCULATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.