2002-11-06 00:00:00************** UNSAT *****************
  
  
  
  
  
 1)NOTE: PLEASE SHOW HEIGHT REQ`MENTS
 FOR FHAR 24CFR 100.205
  
 2)NOTE: PLEASE NOTE< AHU/WATER HEATER
 MAY REQUIRE DISC`S. NOT ALL "LOCK OFF"
 DEVICES ARE APPROVED BY THE CITY OF
 WEST PALM BEACH/AHJ.PLEASE NOTE THAT
 ANY "LOCK OFF " DEVICE MUST BE APPROVED
 BY THE CHIEF ELECTRICAL INSPECTOR.
  
 3)NOTE: PLEASE NOTE RANGE SHOWN AT 12KW
 AND THEN AT 70% AS 5.6KW? PLEASE CLARIFY
  
 4)NOTE; PLEASE 210-52H FOR HALLWAY
 OUTLETS.
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FOR "HOUSE" PANEL.
 MAIN TO PANEL.
  
 6)NOTE: PLEASE SHOW/NOTE MAINS FOR
 UNIT ON RISER/METER DIAGRAM.
  
 7)NOTE: PLEASE NOTE MISSING RECEPT FOR
 A/C COND UNITS. 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  