2003-08-06 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-T2.1 CLEANOUTS REQUIRED PER SEC
 708.3.2 & 708.3.3. ALSO SHOW ON RISER
 DIAGRAM SHT P-T2.2
 2) SHT P-T2.3 STILL HAS ORIGINAL BLDG.
 DRAIN RISER DIAGRAM AND WATER RISER
 DIAGRAMS. REVISION FOR THESE HAS BEEN
 SUBMITTED ON SHT P-T2.2. THESE REVISIONS
 SHOULD BE SUBMITTED ON THE ORIG. SHEETS
 THAT THEY WERE ORIGINALLY APPROVED ON TO
 AVOID CONFUSION. ALSO ROOF PLAN HAS BEEN
 DELETED ON SHT P-T2.2. PLEASE CLAIRFY.
 ---COMMENTS 3) THRU 6) --- SEE COMMENTS
 ON PERMIT # 02100705
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]