Plan Review Notes
Plan Review Notes For Permit 02100708
Permit Number 02100708
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-31 00:00:00DENIED:TYPE II
  
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1. NOTES CONCERNING THE DRYER & TOILET
 EXHAUSTARE NO CLEAR.PLAN SHEET
 AC-U3 NOTE INDICATES SHAFT TO START
 AT THE 2ND FLOOR AT THE ELECTRICAL
 CLOSET?DETAIL ON PLAN SHEET AC-D1
 INDICATES A 1 HR RATED CAULK.PLAN
 SHEET A-DT1 SHOWS A 1 HR SHAFT DETAIL
 FOR THE TOILET & DRYER EXHAUST.
  
 PLEASE PROVIDE A RESIER DETAIL
 SHOWING WHERE THE SHAFT BEGINS &
 ENDS.REFERNECE PLAN SHEET A-DT1
 (SHAFT DETAIL)ON THE MECHANICAL PLAN.
  
 2. PLAN SHEET AC-D1 IN THE NOTE #2,
 STATES DRYER EXHASUT DISCHARGE ON
 ROOF SHALL BE SIMILAR TO TOILET EX
 DISCHARGE BUT SHALL NOT BE SCREENDED.
 AS PER 2001 FBC(M) 504.4, SHALL
 TERMINATE ON THE OUTSIDE OF THE
 BUILDING & SHALL BE EQUIPPED WITH A
 BACKDRAFT DAMPER.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) 402.2
 FOR NATURAL VENTILATION OR TABLE
 403.3.PROVIDE CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.