Plan Review Notes
Plan Review Notes For Permit 02100708
Permit Number 02100708
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-06 00:00:00************* UNSAT *********** *******
  
 1)NOTE: PLEASE SHOW HEIGHT REQ`MENTS
 PER FHAR 24 CFR 100.205
  
 2)NOTE: PLEASE NOTE AHU`S/WATER HEATERS
 MAY REQUIRE DISC`S. PLEASE NOTE NOT ALL
 "LOCK OFF" DEVICES ARE APPROVED BY THE
 CITY OF WEST PALM BEACH. THE "LOCK OUT"
 DEVICE MUST BE APPROVED BY THE CHIEF
 ELECTRICAL INSPECTOR.
  
 3)NOTE: PLEASE CLARIFY 12KW OF HEAT @70%
 IS = TO 5.6 KW?
 PLEASE ADJUST.
  
 4)NOTE: PLEASE NOTE OUTLET SPACING FOR
 HALLWAYS TO MEET 210-52H
  
 5)NOTE: PLEASE NOTE MISSSING OUTLETS
 FOR A/C COND UNITS.210-63
  
 6)NOTE: PLEASE SHOW EQUIPNET GROUNDING
 BETWEEN MAIN AND HOUSE PANEL. 250-122
  
 7)NOTE: PLEASE SHOWMAINS ON METER/MAIN
 RISERD DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372