| Plan Review Notes For Permit 02100708 |
| Permit Number |
02100708 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-06 00:00:00 | ************* UNSAT *********** ******* | | | | | | 1)NOTE: PLEASE SHOW HEIGHT REQ`MENTS | | | PER FHAR 24 CFR 100.205 | | | | | | 2)NOTE: PLEASE NOTE AHU`S/WATER HEATERS | | | MAY REQUIRE DISC`S. PLEASE NOTE NOT ALL | | | "LOCK OFF" DEVICES ARE APPROVED BY THE | | | CITY OF WEST PALM BEACH. THE "LOCK OUT" | | | DEVICE MUST BE APPROVED BY THE CHIEF | | | ELECTRICAL INSPECTOR. | | | | | | 3)NOTE: PLEASE CLARIFY 12KW OF HEAT @70% | | | IS = TO 5.6 KW? | | | PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE NOTE OUTLET SPACING FOR | | | HALLWAYS TO MEET 210-52H | | | | | | 5)NOTE: PLEASE NOTE MISSSING OUTLETS | | | FOR A/C COND UNITS.210-63 | | | | | | 6)NOTE: PLEASE SHOW EQUIPNET GROUNDING | | | BETWEEN MAIN AND HOUSE PANEL. 250-122 | | | | | | 7)NOTE: PLEASE SHOWMAINS ON METER/MAIN | | | RISERD DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEYPALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|