| Plan Review Notes For Permit 02100705 |
| Permit Number |
02100705 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2003-11-18 00:00:00 | PLEASE NOTE PLAN SHEET AC-DT2 IS DENIED. | | | PLAN OMITTED DETAIL OF SHAFT FOR THE | | | REFRIGERATION LINES.AS PER ASHRAE | | | 15-92 SECTION 11.12.3 REFRIGERANT PIPING | | | SHALL NOT BE INSTALLEDD VERTICALLY | | | THROUGH FLOORS FROM ONE STORY TO ANOTHER | | | EXCEPT AS FOLLOWS: | | | (B) IN APPROVED REGID, TIGHT AND | | | CONTINUOUS FIRE-RESISTING PIPE DUCT OR | | | SHAFT. ON THE OUTER WALL OF THE BUILDING | | | (NOT IN AIR SHAFT OR CLOSED COURT).THE | | | SHAFT SHALL BE VENTED TO THE OUTSIDE OR | | | TO THE SPACE SERVED BY THE SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|