| Plan Review Notes For Permit 02100705 |
| Permit Number |
02100705 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-09-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P-T1.1 - REVISION #3 NOT FOUND. | | | PLEASE CLAIRFY. | | | 2) SHT P-T1.2 - REVISIONS # 1, & 2 NOT | | | FOUND. PLEASE CLAIRFY. | | | 3) SHT P-T1.3 - REVISION #3 NOT FOUND. | | | PLEASE CLAIRFY. | | | 4) SHT P-D1 THERMAL EXPANSION CONTROL, | | | SUBMIT MANUF. SPECIFICATION SHEET ON | | | THERMAL EXPANSION VALVE TO SHOW CAPABIL- | | | ITY OF CONTROLLING EXPANSION FOR ALL 20 | | | UNITS. | | | 4) SHT P-D1 RELIEF VALVE DISCHARGE LINE | | | (P/T AND EMERGENCY PAN DRAIN LINES | | | SHALL BE 2" UNDERGROUND PER SECTION | | | 710.3 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|