| Date |
Text |
| 2003-08-06 00:00:00 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) SHT P-T1.1 CLEANOUTS REQUIRED PER SEC |
| | 708.3.2 & 708.3.2. ALSO SHOW ON RISER |
| | DIAGRAM SHT P-T1.2 |
| | 2) SHT P-T1.3 STILL HAS ORIGINAL BLDG. |
| | DRAIN RISER DIAGRAM AND WATER RISER |
| | DIAGRAMS. REVISION FOR THESE HAS BEEN |
| | SUBMITTED ON SHT P-T1.2. THESE REVISIONS |
| | SHOULD BE SUBMITTED ON THE ORIG. SHEETS |
| | THAT THEY WERE ORIGINALLY APPROVED ON TO |
| | AVOID CONFUSION. ALSO ROOF PLAN HAS BEEN |
| | DELETED ON SHT P-T1.2 PLEASE CLAIRFY. |
| | 3) SHT P-D1 CONDENSATE DRAIN LINE SHALL |
| | NOT BE TRAPPED. SECTION 1002.6 |
| | 4) SHT P-D1 THERMAL EXPANSION CONTROL |
| | SHALL BE ADDRESSED. INFORMATION HAS BEEN |
| | DELETED FROM ORIGINAL SHEET. SECTION |
| | 607.3.2 |
| | 5) SHT P-D1 CONDENSATE RISERS HAVE BEEN |
| | DELETED. |
| | - SIZE EMERGENCY PAN DRAIN LINES FOR |
| | WATER HEATER. |
| | - NOTE #6 AT WATER RISER DIAGRAMS RE- |
| | FERS TO SHEET P-6.2. THIS SHEET HAS NOT |
| | BEEN FOUND. PLEASE CLAIRFY. |
| | - GENERAL PLUMBING NOTES: DRAINAGE |
| | PIPING FOR WATER HEATER PANS SHALL BE |
| | CPVC. |
| | 6) SHT P-D1 THE WATER HEATER EMERGENCY |
| | PAN SHALL BE OF SUFFICIENT SIZE & SHAPE |
| | TO RECIEVE ALL DRIPPING OR CONDENSATE |
| | FROM THE TANK OR WATER HEATER. SECTION |
| | 504.8.1. ALSO THE PAN SHALL BE OF SUFFI- |
| | CIENT SIZE AND SHAPE TO RECIEVE THE DIS- |
| | CHARGE OF THE RELIEF VALVE DISCHARGE, & |
| | AS TO NOT BLOCK THE PAN DRAIN. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |