Plan Review Notes
Plan Review Notes For Permit 02100705
Permit Number 02100705
Review Stop P
Sequence Number 4
Notes
Date Text
2003-08-06 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-T1.1 CLEANOUTS REQUIRED PER SEC
 708.3.2 & 708.3.2. ALSO SHOW ON RISER
 DIAGRAM SHT P-T1.2
 2) SHT P-T1.3 STILL HAS ORIGINAL BLDG.
 DRAIN RISER DIAGRAM AND WATER RISER
 DIAGRAMS. REVISION FOR THESE HAS BEEN
 SUBMITTED ON SHT P-T1.2. THESE REVISIONS
 SHOULD BE SUBMITTED ON THE ORIG. SHEETS
 THAT THEY WERE ORIGINALLY APPROVED ON TO
 AVOID CONFUSION. ALSO ROOF PLAN HAS BEEN
 DELETED ON SHT P-T1.2 PLEASE CLAIRFY.
 3) SHT P-D1 CONDENSATE DRAIN LINE SHALL
 NOT BE TRAPPED. SECTION 1002.6
 4) SHT P-D1 THERMAL EXPANSION CONTROL
 SHALL BE ADDRESSED. INFORMATION HAS BEEN
 DELETED FROM ORIGINAL SHEET. SECTION
 607.3.2
 5) SHT P-D1 CONDENSATE RISERS HAVE BEEN
 DELETED.
 - SIZE EMERGENCY PAN DRAIN LINES FOR
 WATER HEATER.
 - NOTE #6 AT WATER RISER DIAGRAMS RE-
 FERS TO SHEET P-6.2. THIS SHEET HAS NOT
 BEEN FOUND. PLEASE CLAIRFY.
 - GENERAL PLUMBING NOTES: DRAINAGE
 PIPING FOR WATER HEATER PANS SHALL BE
 CPVC.
 6) SHT P-D1 THE WATER HEATER EMERGENCY
 PAN SHALL BE OF SUFFICIENT SIZE & SHAPE
 TO RECIEVE ALL DRIPPING OR CONDENSATE
 FROM THE TANK OR WATER HEATER. SECTION
 504.8.1. ALSO THE PAN SHALL BE OF SUFFI-
 CIENT SIZE AND SHAPE TO RECIEVE THE DIS-
 CHARGE OF THE RELIEF VALVE DISCHARGE, &
 AS TO NOT BLOCK THE PAN DRAIN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]