2003-02-19 00:00:00PROVISO:TYPE I
 1. PLAN SHEET AC-DI GE WASHER/DRYER
 MODEL SPECIFICATIONS, SPECS INDICATE
 ELECTRIC & GAS DRYERS, SHOULD GAS DRYERS
 BE INSTALLED CALCULATIONS FOR COMBUSTION
 AIR WILL BE REQUIRED.
  
 2. PLAN SHEET AC-D2 DETIAL FOR TOILET
 EXHAUST, AS PER 2001 FBC(M) 607.4,
 DUCTS EXTENDING THROUGH MORE THAN ONE
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE HAVING A FIRE RESISTANCE
 RATING OF 1HR FOR BUILDINGS LESS THAN
 4 STORIES & 2HR FOR BUILDINGS GREATER
 THAN 4 STORIES.
  