| Plan Review Notes For Permit 02100705 |
| Permit Number |
02100705 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-27 00:00:00 | 1) PLEASE SEE BUILDING PLAN REVIEW | | | COMMENTS REGARDING THE STIPULATIONS | | | PROVIDED TO THE DESIGNERS BY THE | | | CONSTRUCTION BOARD OF ADJUSTMENT AND | | | APPEALS ON 1/8/03. | | | | | | 2) THE FIRE SPRINKLER SYSTEM SHALL | | | MEET NFPA 13 REQUIREMENTS NOT 13R | | | REQUIREMENTS. | | | | | | 3) ALL OPENINGS THAT FIRE AND | | | PARAMEDICAL EQUIPMENT ARE EXPECTED TO | | | USE SHALL BE AT LEAST 20 FEET IN | | | CLEAR WIDTH. | | | | | | 4) EXHAUST FLOOR PENETRATION DETAIL | | | ON AC-D2 NOT SHOWN AS BEING FIRE RATED. | | | | | | 5) BUILDING ADDRESSES REQUIRED ON | | | BUILDING. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|