| Notes |
| Date |
Text |
| 2003-02-20 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLANS MENTION F/A DEVICES TO | | | MEET ADA BUT PLEASE SHOW/ NOTE HEIGHTS | | | FOR ELECTRICAL DEVICES. PER FHAR. | | | | | | 2)NOTE: PLEASE INDICATE MAIN BRKR/OCP AT | | | METER BANK LOCATION FOR UNITS. SHOW ON | | | RISER DIAGRAM. | | | | | | 3)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS FROM NEW SETS. | | | | | | PLEASE NOTE, THE NOTES ABOVE ARE FROM | | | FIRST REVIEW. PLEASE SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW.IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: RANGE IS STILL SHOWN AT 5.6KW?? | | | SHOWN AS 12KW, THEN DERATED AT 70%,, | | | PLEASE RE-CONFIGURE. |
|