| Plan Review Notes For Permit 02100705 |
| Permit Number |
02100705 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FHA-AMEND 98 DESIGN MANUAL | | | | | | 1) SHTS A-U2 & A-U3, INDICATE ON PLANS | | | SPECIFICATION "A" OR "B" FOR BATHROOMS | | | PER REQUIREMENT 7B PAGE 7.35 DESIGN | | | MANUAL FHA-98 | | | 2) SHT ADT-II BACKING FOR W/C'S AND TUBS | | | TO BE ACCORDING TO REQUIREMENT 6 PAGE | | | 6.9 DESIGN MANUAL FHA-98 | | | 3) SHT ADT-II THE TOP OF LAV FIXTURE RIM | | | IS A MAXIMUM OF 2'10" ABOVE FINISHED | | | FLOOR. PLEASE INDICATE ON BATHROOM DE- | | | TAIL. | | | 4) SHT P-U2 DOMESTIC WATER RISER, LOCATE | | | WATER HAMMER ARRESTORS AT WASH MACHINE | | | NEAR FIXTURE, NOT AT THE TOP OF THE DROP | | | 5) SHT P-T1.1 BLDG. DRAIN CLEAN OUTS | | | MAXIMUM OF 100'. TWO WAY C/O REQUIRED IN | | | THE BREEZEWAY SEC 708.3.1. ALSO SHOW C/O | | | ON SANITARY RISER DIAGRAM SHT P-T1.3 | | | 6) SHT P-D1 PLUMBING GENERAL NOTES #6, | | | DIELECTRIC UNIONS NOT APPROVED FOR WATER | | | USAGE. PLEASE DELETE REFERENCE. | | | 7) SHT P-D1 WATER HEATER DETAIL, THE | | | RELIEF VALVE DISCHARGE PIPE SHALL NOT | | | HAVE ANY TRAPPED SECTIONS. SEC 504.7.1 | | | THERMAL EXPANSION CONTROL IS ALSO RE- | | | QUIRED. SECTION 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|