2002-10-31 00:00:00DENIED:TYPE I
  
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.NOTES CONCERNING THE DRYER & TOILET
 EXHAUST ARE NOT CLEAR.PLAN SHEET
 AC-U3 NOTE INDICATES SHAFT TO START
 AT THE 2ND FLOOR AT THE ELECTRICAL
 CLOSET?DETAIL ON PLAN SHEET AC-D1
 INDICATES A 1 HR RATED CAULK.PLAN
 SHEET A-DT1 SHOWS A 1 HR SHAFT
 DETAIL FOR THE TOILET & DRYER
 EXHAUST.
  
 PLEASE PROVIDE A RISER DETAIL
 SHOWING WHERE THE SHAFT BEGINS &
 ENDS. REFERENCE PLAN SHEET A-DT1,
 (SHAFT DETAIL)ON THE MECHANICAL PLAN
  
 2.PLAN SHEET AC-D1 IN THE NOTE #2,
 STATES DRYER EXHAUST DISCHARGE ON
 ROOF SHALL BE SIMILAR TO TOILET EX
 DISCHARGE BUT SHALL NOT BE SCREENED.
 AS PER 2001 FBC(M) 504.4, SHALL
 TERMINATE ON THE OUTSIDE OF THE
 BUILDING & SHALL BE EQUIPPED WITH A
 BACKDRAFT DAMPER.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) 402.2
 FOR NATURAL VENTILATION OR TABLE
 403.3.PROVIDE CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.