Plan Review Notes
Plan Review Notes For Permit 02100705
Permit Number 02100705
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-08 00:00:001) BUILDING ADDRESSES REQUIRED ON
 BUILDING.
  
 2) FIRE SPRINKLER DRAWINGS ARE REQUIRED
 AT TIME OF PERMIT SUBMITTAL. ALL
 BUILDINGS THREE STORIES OR GREATER ARE
 REQUIRED TO BE FIRE SPRINKLER PROTECTED
 PER FS 553.895(2).
  
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 4) WHAT PROVISIONS ARE TO BE MADE WITH
 REGARDS TO FIRE AND PARAMEDICAL ACCESS.
 THRU THE SECURITY GATES. IF SECURITY
 GATES ARE ELECTRIC, WHAT PROVISIONS
 HAVE BEEN MADE IN THE EVENT OF LOSS
 OF POWER.
  
 5) ALL OPENINGS IN WHICH FIRE RESCUE
 VEHICLES ARE EXPECTED TO PASS, SHALL
 BE AT LEAST TWENTY FEET IN CLEAR
 WIDTH. SEPARATE PERMIT REQUIRED.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATIONS.
  
 7) ELECTRIC POWERED SMOKE DETECTORS
 SHALL NOT BE INSTALLED CLOSER THAN
 THREE FEET FROM AIR CONDITIONER
 DIFFUSERS.
  
 8) PLEASE PROVIDE A LIFE SAFETY PLAN
 WITH REGARDS TO EXITING FOR REVIEW.
  
 9) NO EMERGENCY LIGHTING SHOWN OF
 SIDE EXIT STAIRS.
  
 10) ARE THERE ANY WINDOWS WITHIN 10
 FEET OF THE SINGLE EXIT STAIRS.
  
 11) NO PROPANE GRILLS ARE ALLOWED ON
 EXTERIOR PATIO'S.
  
 12) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved