| Date |
Text |
| 2002-11-08 00:00:00 | 1) BUILDING ADDRESSES REQUIRED ON |
| | BUILDING. |
| | |
| | 2) FIRE SPRINKLER DRAWINGS ARE REQUIRED |
| | AT TIME OF PERMIT SUBMITTAL. ALL |
| | BUILDINGS THREE STORIES OR GREATER ARE |
| | REQUIRED TO BE FIRE SPRINKLER PROTECTED |
| | PER FS 553.895(2). |
| | |
| | 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 4) WHAT PROVISIONS ARE TO BE MADE WITH |
| | REGARDS TO FIRE AND PARAMEDICAL ACCESS. |
| | THRU THE SECURITY GATES. IF SECURITY |
| | GATES ARE ELECTRIC, WHAT PROVISIONS |
| | HAVE BEEN MADE IN THE EVENT OF LOSS |
| | OF POWER. |
| | |
| | 5) ALL OPENINGS IN WHICH FIRE RESCUE |
| | VEHICLES ARE EXPECTED TO PASS, SHALL |
| | BE AT LEAST TWENTY FEET IN CLEAR |
| | WIDTH. SEPARATE PERMIT REQUIRED. |
| | |
| | 6) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM INSTALLATIONS. |
| | |
| | 7) ELECTRIC POWERED SMOKE DETECTORS |
| | SHALL NOT BE INSTALLED CLOSER THAN |
| | THREE FEET FROM AIR CONDITIONER |
| | DIFFUSERS. |
| | |
| | 8) PLEASE PROVIDE A LIFE SAFETY PLAN |
| | WITH REGARDS TO EXITING FOR REVIEW. |
| | |
| | 9) NO EMERGENCY LIGHTING SHOWN OF |
| | SIDE EXIT STAIRS. |
| | |
| | 10) ARE THERE ANY WINDOWS WITHIN 10 |
| | FEET OF THE SINGLE EXIT STAIRS. |
| | |
| | 11) NO PROPANE GRILLS ARE ALLOWED ON |
| | EXTERIOR PATIO'S. |
| | |
| | 12) PLEASE PROVIDE PRESCRIPTIVE CODE |
| | REQUIREMENTS FOR ALL HANDRAILS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |