Plan Review Notes
Plan Review Notes For Permit 02100705
Permit Number 02100705
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-06 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE SIZING FOR FEEDER
 TO BE SIZE FOR 100A. SHOWN AS EITHER
 #2 OR #4. PLEASE NOTE ONLY #2 IS SIZED
 CORRECTLY. 310-16/110-14
  
 2)NOTE: PLEASE NOTE, AHU/WATER HEATER
 MAY REQUIRE DISC`S. NOT ALL "LOCK OFF"
 DEVICES ARE APPROVED BY THE CITY OF
 WEST PALM BEACH/AHJ. PLEASE NOTE ANY
 LOCK OFF DEVICE MUST BE APPROVE BY
 CHEIF ELECTRICAL INSPECTOR.
  
 3)NOTE: PLEASE SHOW HEIGHT REQ`MENTS
 PER FHAR 24CFR 100.205.
  
 4)NOTE: PLEASE NOTE RANGE IS SHOWN AT
 12KW AND THEN AT 70%. PLEASE NOTE, 70%
 IS SHOWN AT 5.6KW?? PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING FOR "H" PANEL.
 250-122
  
 6)NOTE: PLEASE SHOW/NOTE MAINS ON METER
 RISER DIAGRAM.
  
 7)NOTE: PLEASE NOTE MISSING HALLWAY
 OUTLETS PER 210-52H
  
 8)NOTE: PLEASE SHOW RECEPTS FOR A/C UNIT
 -S PER 210-63.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372