| 2002-11-01 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. |
| | |
| | |
| | |
| | THE EGRESS STAIRS ARE REQUIRED TO BE |
| | ENCLOSED IN FIRE RESISTANT CONSTRUCTION |
| | IN ACCORDANCE WITH FBC 1006.1.1. |
| | |
| | THE EXTERIOR STAIRS ON THE ENDS OF THE |
| | BUILDING MUST BE SERVED BY A 4.5' WIDE |
| | BALCONY NOT THE 4.0' SHOWN.SEE FBC |
| | 1006.2.2. |
| | |
| | THE ROOF TILE FASTENING METHOD DESCRIBED |
| | ON SHEET AT 1.2 DOES NOT COMPLY WITH |
| | FBC 1507.4. |
| | |
| | THE FIRE SPRINKLER DESIGN MUST ACCOMPANY |
| | THE PERMIT PLANS.SEE FBC 104.3. |
| | |
| | THE ATTIC VENTILATION AREAS DECLARED ON |
| | SHEET A-T1.2 WHEN COMPARED TO THE NUMBER |
| | AND SIZE OF VENTS TO BE USED DOES NOT |
| | SEEM PRACTICAL IN THAT THE VENTS WOULD |
| | HAVE TO PROVIDE 80 % TO 90 % OF FREE |
| | AREA.PLEASE CLARIFY. |
| | |
| | THE ALUMINUM RAILING INFORMATION ON |
| | SHEET A-DT9 #3 DIRECTS DESIGN TO |
| | CHAPTER 23 (WOOD) OF THE FBC.SEE THE |
| | RESPONSIBILITY RULES FOR ENGINEERS FOR |
| | DELEGATED DESIGN. CHAPTER 61G15-31 |
| | |
| | SHEET ADT7 HAS SEVERAL DETAILS FOR THE |
| | ATTACHMENT OF WINDOW AND DOOR FRAMES TO |
| | THE 5" CONCRETE PANELS.IT APPEARS |
| | THAT THE EDGE DISTANCE FOR THE TAPCON |
| | TYPE OF FASTENERS SHOULD BE |
| | INVESTIGATED AND THE DESIGN LOAD |
| | DECLARED. |
| | |
| | THE SHUTTERS CITED ON SHEET ADT1 MUST |
| | BBE OF THE PERMANENTLY AFFIXED TYPE IE, |
| | ACCORDION, ROLL UP, ETC. AND NOT |
| | REMOVABLE PANELS AS PROVIDED FOR IN THE |
| | BUILDING OFFICIAL'S IMPLEMENTATION |
| | STANDARD FOR THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE AND A COPY OF |
| | THE PAID RECEIPT ATTCHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | A RECENT SURVEY MUST ACCOMPANY THE |
| | PERMIT APPLICATION.(A PORTION OF THE |
| | PROPERTY MAY BE LOCATED IN THE FLOOD |
| | HAZARD AREA) |
| | |
| | THE AS-1 SITE PLAN IS TOO SMALL OF A |
| | SCALE TO BE COMPLETELY LEGIBLE. |
| | |
| | IF TEST REPORTS AND PRODUCT ACCEPTANCE |
| | REPORTS FOR THE ROOF COVERINGS WINDOWS |
| | AND DOORS ARE NOT INCLUDED WITH THE |
| | PERMIT APPLICATION, SEPARATE PERMITS, |
| | FEES AND PLANS WILL BE REQUIRED FOR |
| | THAT WORK. |
| | |
| | THESE NOTES MAY APPLY TO THE BUILDING TY |
| | PES I, II, III, IV AND V |