Plan Review Notes
Plan Review Notes For Permit 02100692
Permit Number 02100692
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-01 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE NOTE ON THE RISER DIAGRAM SHOWS 2
 4/0 CU & 1-2/0 CU GROUND.
  
 A) THERE CAN BE NO EQ."GROUND" FROM
 THE METER TO THE DISCONNECT.
  
 B) THERE MUST BE AN EQUIPMENT GROUND
 FROM THE DISCONNECT TO THE PANEL.
  
 C) THERE MUST BE A NEUTRAL TO BOTH,
 PLEASE CLARIFY.
  
 3} THE #4 G.E.C. MUST BE A #1/OCU PER
 250-66,AND MUST HAVE A GROUND ROD IN
 THE SYSTEM PER 250-50(A)(2).
  
 4} RECEPTACLES MUST BE PROVIDED ON THE
 COUNTERTOPS TO THE WEST & EAST SIDE
 OF THE NORTH KITCHEN DOORS TO COMPLY
 WITH 210-52(C)(1).
  
 5} THE RECEPTACLE FOR THE JACUZZI MUST
 GFCI PROTECTED PER 680-70.
  
 6} THERE MUST BE A RECEPTACLE LOCATED IN
 THE ATTIC TO SERVICE THE AHU PER 210-
 63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392