| 2002-11-01 00:00:00 | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | TO THE PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} THE NOTE ON THE RISER DIAGRAM SHOWS 2 |
| | 4/0 CU & 1-2/0 CU GROUND. |
| | |
| | A) THERE CAN BE NO EQ."GROUND" FROM |
| | THE METER TO THE DISCONNECT. |
| | |
| | B) THERE MUST BE AN EQUIPMENT GROUND |
| | FROM THE DISCONNECT TO THE PANEL. |
| | |
| | C) THERE MUST BE A NEUTRAL TO BOTH, |
| | PLEASE CLARIFY. |
| | |
| | 3} THE #4 G.E.C. MUST BE A #1/OCU PER |
| | 250-66,AND MUST HAVE A GROUND ROD IN |
| | THE SYSTEM PER 250-50(A)(2). |
| | |
| | 4} RECEPTACLES MUST BE PROVIDED ON THE |
| | COUNTERTOPS TO THE WEST & EAST SIDE |
| | OF THE NORTH KITCHEN DOORS TO COMPLY |
| | WITH 210-52(C)(1). |
| | |
| | 5} THE RECEPTACLE FOR THE JACUZZI MUST |
| | GFCI PROTECTED PER 680-70. |
| | |
| | 6} THERE MUST BE A RECEPTACLE LOCATED IN |
| | THE ATTIC TO SERVICE THE AHU PER 210- |
| | 63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT. 8392 |