Plan Review Notes
Plan Review Notes For Permit 02100692
Permit Number 02100692
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 1804.2.2SUBMIT A SOIL REPORT
 FROM A FLORIDA LICENSED DESIGN
 PROFESSIONAL.
  
 2) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 3) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 - FRAMELESS MASTER BATH SHOWER DOOR
 - THE THREE WINDOWS ABOVE THE JACUZZI
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 4) FBC 2309.6THE ATTIC ACCESS SHOWN
 SHALL PROVIDE ACCESS TO ALL ATTIC SPACES
 WITH A CLEAR HEIGHT OF NOT LESS THAN 24"
 OR ADDITIONAL ATTIC ACCESS OPENINGS WILL
 BE REQUIRED.
  
 5) FBC 2309.7ATTIC SPACE VENTILATION.
 THE CEILING INSULATION SHALL BE CLEAR OF
 THE UNDERSIDE OF THE ROOF DECKING SUCH
 THAT THE ATTIC SPACE VENTILATION IS
 MAINTAINED (REF SHEETS A-5 AND A-6, WALL
 SECTIONS)
  
 6) FBC 1007.3.3EXTERNAL STEP DETAIL,
 SHEET A-6.RISERS SHALL BE OF UNIFORM
 HEIGHT.THE TOP RISER HEIGHT SHOWN ON
 THE DETAIL IS 2" LESS THAN THE
 REMAINING RISERS.AMEND THE DETAIL.
  
 7) FBC 1012.1.5STEPS OUTSIDE FAMILY
 ROOM FRENCH DOORS.THERE SHALL BE NO
 MORE THAN ONE STEP (7" RISE, MAX.)
 BEFORE A LANDING OR GRADE ON THE
 EXTERIOR SIDE OF THE DOORS.AMEND THE
 PLANS.
  
 8) FLOOR TRUSS ANCHORS.WALL SECTION
 1/A-5 SHOWS USP HC-10 ANCHORS BETWEEN
 THE FLOOR TRUSS AND CONCRETE TIE BEAM.
 USP HC-10 ANCHORS ARE FOR CONECTIONS
 BETWEEN TRUSSES AND WOOD PLATES NOT
 CONCRETE. SPECIFY AN APPROPRIATE ANCHOR.
  
 9) PGT INDUSTRIES' SINGLE HUNG WINDOW
 PRODUCT APPROVAL NOA# 01-0629.08 COVERS
 SINGLE UNIT APPLICATIONS ONLY (SEE NOA
 SHEET 2, ITEM 3.1).SUBMIT A PRODUCT
 APPROVAL FOR AN APPROPRIATE WINDOW
 MULLION TO SUIT THE MULLED BREAKFAST
 ROOM, FAMILY ROOM AND MASTER BEDROOM
 WINDOWS.
  
 10) FBC* 104.2.1.2NEW 4"X 4" STEEL
 COLUMNS (DETAIL 2/A-2) ARE SPECIFIED
 WITHOUT REFERENCE TO CORROSION
 PROTECTION, ABOVE GROUND OR IN CONTACT
 WITH THE GROUND.AMEND THE PLANS TO
 STATE THE MEANS OF CORROSION PROTECTION.
  
 11) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499