2002-12-13 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02100668
 ADDRESS: 4821 N FLAGLER DR
 CONT: P M WRIGHT
 TELL # (561)309-6162
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO******
  
 1) FD-101 OUTSWING ALUMINIUM FRENCH DOOR
 PRODUCT APPROVAL INDICATES "NO LARGE
 MISSLE IMPACT TESTING" STORM SHUTTERS
 ARE REQUIRED, SHALL REQUIRE A SEPERATE
 PERMIT, PRODUCT TESTING REPORT & REVIEW.
 2) A5 FLOOD ZONE- LAW DEPARTMENT HAS
 DETERMINED THAT ADDITIONS THAT ARE UNDER
 50% OF THE BUILDING VALUE ARE NOT CONSID
 ERED NEW WORK BUT RENOVATIONS,EXEMPTING
 THE RESIDENCE FROM THE CITY FLOOD ZONE
 ORDINANCE REQUIREMENT OF 7'-6" MINIMUM
 FINISH FLOOR ELEVATION FOR A A-5 FLOOD
 ZONE.
 BUILDING PLAN REVIEW
 JIM WITMER