| Plan Review Notes For Permit 02100668 |
| Permit Number |
02100668 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-28 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO PLANS AND RESUBMIT FOR REVISION. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} METER SHOWN AS "EXISTING" MUST BE | | | RATED FOR THE AMPERAGE AND AIC OF THE | | | NEW SERVICE. | | | | | | 3} PLEASE SUBMIT LOAD CALCAULATIONS | | | PER 220,215-5.INDICATE EXISTING AND | | | NEW CALCS. | | | | | | 4} SUBMIT RISER DIAGRAM FOR NEW SERVICE | | | & INDICATE TYPE OF G.E.C SYSTEM BEING | | | USED PER 250-50. | | | | | | 5} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.SHOW RECEPTACLE | | | ON THE DRAWING IN THE ADDED BATH. | | | | | | 6} LIST SMALL APPLIANCE CIRCUITS PER | | | 210-11(C)(1),INCLUDE IN CALCULATIONS. | | | | | | 7} LIST REQUIRED LAUNDRY CIRCUIT ON THE | | | PANEL SCHEDULE AND IN THE CALCULATIONS. | | | | | | 8} PLEASE ADD PENINSULAR RECEPTACLE PER | | | 210-52(C)(3). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|