Plan Review Notes
Plan Review Notes For Permit 02100668
Permit Number 02100668
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVISION.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} METER SHOWN AS "EXISTING" MUST BE
 RATED FOR THE AMPERAGE AND AIC OF THE
 NEW SERVICE.
  
 3} PLEASE SUBMIT LOAD CALCAULATIONS
 PER 220,215-5.INDICATE EXISTING AND
 NEW CALCS.
  
 4} SUBMIT RISER DIAGRAM FOR NEW SERVICE
 & INDICATE TYPE OF G.E.C SYSTEM BEING
 USED PER 250-50.
  
 5} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.SHOW RECEPTACLE
 ON THE DRAWING IN THE ADDED BATH.
  
 6} LIST SMALL APPLIANCE CIRCUITS PER
 210-11(C)(1),INCLUDE IN CALCULATIONS.
  
 7} LIST REQUIRED LAUNDRY CIRCUIT ON THE
 PANEL SCHEDULE AND IN THE CALCULATIONS.
  
 8} PLEASE ADD PENINSULAR RECEPTACLE PER
 210-52(C)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392