Plan Review Notes
Plan Review Notes For Permit 02100668
Permit Number 02100668
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02100668
 ADD: 4821 S FLAGLER DR
 CONT: P. M. WRIGHT CONSTRUCTION
 TEL: (561)863-5088
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 3109.1.3 FLOODPLAIN CONSTRUCTION
 SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 12, FLOOD PREVENTION AND CONTROL
 OF THE CODE OF THE CITY OF WEST PALM
 BEACH.
  
 CHAP 12 SEC 12-22 PROVISIONS FOR
 FLOOD HAZARD REDUCTION,(B)(1) ALL NEW
 CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT
 OF ANY EXISTING RESIDENTIAL STRUCTURE
 SHALL HAVE THE LOWEST FLOOR, INCLUDING
 BASEMENT, ELEVATED TO SIX(6) INCHES
 ABOVE THE FLOOD ELEVATION (7'-6").
  
 CHAP 12 SEC 12-17 DEFINITIONS:
 SUBSTANTIAL IMPROVEMENTS: MEANS ANY COM-
 BINATION OF REPAIRS, RECONSTRUCTION,
 ALTERATION,OR IMPROVEMENTS TO A STRUC-
 TURE, TAKING PLACE DURING THE LIFE OF A
 STRUCTURE IN WHICH THE CUMULATIVE COST
 EQUALS OR EXCEEDS FIFTY PER CENT OF THE
 MARKET VALUE OF THE STRUCTURE.
  
 PROPERTY APPRAISERS IMPROVEMENT
 VALUEIS $104,375.00 . THE REMODEL &
 ADDITION VALUE OF THE CURRENT PROJECT IS
 $180,000.00+ OR OVER 50% OF THE IMPROVE-
 MENT VALUE. THIS MEANS THAT THE FLOOR
 LEVEL OF THE EXISTING STRUCTURE PLUS THE
 FLOOR OF THE NEW WORK WOULD BE REQUIRED
 TO BE ABOVE 7'-6" .
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 4)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 5)905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 7)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA. FLAT ROOFED AREA,
 DRAINAGE?
  
 8)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) FRENCH DOORS- IMPACT
 B) SINGLE HUNG- IMPACT
 C) OVERHEAD GARAGE DOOR 9X7, 16X7
 D) MULLIONS- IMPACT/ W CLIPS
 E) ROOFING ASSEMBLIES- BUILT UP ROOF
  
 10) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 12)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36". GARAGE &
 2ND STORY.
  
 13) DISCREPANCY, ENERGY CALCS CEILING
 INSULATION R19 VS A-8 DETAIL R30.
  
 14) SHEET A-6 NOTE# 9 REFRENCES HUGHES
 STRAP, OUT OF BUSINESS:REFRENCE CURRENT
 MANUFACTURER/ MODEL.
  
 15)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 TRUSS ENGINEERING SHEET NOT SIGNED
 & SEALED.
  
 16) SHEET A-7 DETAIL# 1 INDICATES THE
 USE OF 3/4" EXPANSION BOLTS, NO EMBED
 LENGHT OR OVERALL LENGHT IS GIVEN?
  
 17) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-7 DETAIL 2, KNEE WALL, THE FLAT
 ROOF TRUSS & 2X12 RAFTER ARE STRAPED TO
 THE KNEE WALL WITH A MTS16 (1000 LBS)
 UPLIFT, WHILE THE BOTTOM OF THE KNEE
 WALL IS STRAPED WITH A H2.5 (415 LBS)
 CAPACITY OF UPLIFT, WHAT WILL BE THE
 UPLIFT LOADS IMPOSED?
  
 18) SHEET A-8 ALL DETAILS ARE MISSING
 A VAPOR BARRIER REQUIRED FOR MONOLITHIC
 SLABS (DAMPPROOFING) 1814.3.2/1816.1.4
  
 19)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026