Plan Review Notes
Plan Review Notes For Permit 02100667
Permit Number 02100667
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-18 00:00:00THE CONCRETE DESIGN STANDARDS CITED ON
 SHEET A1 ARE OUTDATED AND/OR WRONG
 APPLICATION.SEE FBC 1900 AND FBC 3500
  
 STEEL AND MASONRY, SAME.SEE FBC 2100
 AND FBC 3500.ALSO, PLEASE PROVIDE THE
 DESIGN INFORMATION FOR THE REINFORCED
 MASONRY, IE; F'M, POUR HEIGHTS, GROUT
 SPECIFICATION, TESTS REQUIRED, IF ANY.
  
 THE 16" X 16" MASONRY COLUMN AT THE
 PATIO DEPICTED ON SHEET A2 DOES NOT
 SPECIFY ANY STEEL.PLEASE REVISE AS
 NECESSARY.
  
 FOUNDATION NOTE #5 ON SHEET A2 RE:
 FOOTING DESIGNED IN ACCORDANCE WITH FBC
 2402.2, IS NOT A VALID CODE SECTION.
 MORE IMPORTANTLY, FBC 104.2.1 DOES NOT
 ALLOW CITING OF CODE SECTIONS AS A
 SUBSTITUTE FOR SPECIFIC DESIGN
 INFORMATION.
  
 SHEET A3 SHOW THE DESIGN CRITERIA FOR
 THE DELEGATED DESIGN RESPONSIBILITY FOR
 THE SOFFIT BEAM ON THE PATIO.
  
 SHOW THE WIND DESIGN INFORMATION ON THE
 PLANS IN ACCORDANCE WITH FBC 1606.1.7.