| Plan Review Notes For Permit 02100667 |
| Permit Number |
02100667 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-18 00:00:00 | THE CONCRETE DESIGN STANDARDS CITED ON | | | SHEET A1 ARE OUTDATED AND/OR WRONG | | | APPLICATION.SEE FBC 1900 AND FBC 3500 | | | | | | STEEL AND MASONRY, SAME.SEE FBC 2100 | | | AND FBC 3500.ALSO, PLEASE PROVIDE THE | | | DESIGN INFORMATION FOR THE REINFORCED | | | MASONRY, IE; F'M, POUR HEIGHTS, GROUT | | | SPECIFICATION, TESTS REQUIRED, IF ANY. | | | | | | THE 16" X 16" MASONRY COLUMN AT THE | | | PATIO DEPICTED ON SHEET A2 DOES NOT | | | SPECIFY ANY STEEL.PLEASE REVISE AS | | | NECESSARY. | | | | | | FOUNDATION NOTE #5 ON SHEET A2 RE: | | | FOOTING DESIGNED IN ACCORDANCE WITH FBC | | | 2402.2, IS NOT A VALID CODE SECTION. | | | MORE IMPORTANTLY, FBC 104.2.1 DOES NOT | | | ALLOW CITING OF CODE SECTIONS AS A | | | SUBSTITUTE FOR SPECIFIC DESIGN | | | INFORMATION. | | | | | | SHEET A3 SHOW THE DESIGN CRITERIA FOR | | | THE DELEGATED DESIGN RESPONSIBILITY FOR | | | THE SOFFIT BEAM ON THE PATIO. | | | | | | SHOW THE WIND DESIGN INFORMATION ON THE | | | PLANS IN ACCORDANCE WITH FBC 1606.1.7. |
|