Plan Review Notes
Plan Review Notes For Permit 02100605
Permit Number 02100605
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-29 00:00:00PROVISO:MECHANICAL PERMIT 02100607
  
 PROVIDE SUFFICIENT ROOM FOR ACCESS FOR
 REMOVAL & SERVICING OF THE AHU'S.
 ACCESS SHALL COMPLY WITH 2001 FBC(M)
 306.3 & 306.3.1.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 2001 FBC(M) 606.2.2 WITH NOTIFACTION
 TO ALARM/STROBE AS PERNFPA 90A 4-4.4.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.