| Notes |
| Date |
Text |
| 2002-10-29 00:00:00 | PROVISO:MECHANICAL PERMIT 02100607 | | | | | | PROVIDE SUFFICIENT ROOM FOR ACCESS FOR | | | REMOVAL & SERVICING OF THE AHU'S. | | | ACCESS SHALL COMPLY WITH 2001 FBC(M) | | | 306.3 & 306.3.1. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | | PER 2001 FBC(M) 606.2.2 WITH NOTIFACTION | | | TO ALARM/STROBE AS PERNFPA 90A 4-4.4.3 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|