| Date |
Text |
| 2002-12-04 00:00:00 | PASSED WITH PROVISOS: | | | 1. THE NEW BACKFLOW PREVENTER MUST BE | | | COMPLETELY HIDDEN FROM VIEW WITH SHRUBS | | | PRIOR TO ACTIVATION. COORDINATE WITH | | | CIVIL PLANS FOR THE PROPOSED INLET. | | | 2. A CLEAN OUT WILL NEED TO BE INSTALLED | | | IN THE SANITARY SEWER LATERAL, ON | | | PROPERTY, IF NOT ALREADY INSTALLED. | | | 3. A SEPARATE IRREGATION METER AND BACK- | | | FLOW PREVENTER ON THAT LINE IS | | | RECOMMENDED. | | | 4. ALL INTALLATION TO CITY SERVICES MUST | | | BE PER CITY STANDARDS. 659-8040 | | | 5. ALL BROKEN SIDEWALKS ALONG THE | | | PROPERTY (ALL SIDES) MUST BE REPLACED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|