Plan Review Notes
Plan Review Notes For Permit 02100605
Permit Number 02100605
Review Stop ENG
Sequence Number 1
Notes
Date Text
2002-12-04 00:00:00PASSED WITH PROVISOS:
 1. THE NEW BACKFLOW PREVENTER MUST BE
 COMPLETELY HIDDEN FROM VIEW WITH SHRUBS
 PRIOR TO ACTIVATION. COORDINATE WITH
 CIVIL PLANS FOR THE PROPOSED INLET.
 2. A CLEAN OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON
 PROPERTY, IF NOT ALREADY INSTALLED.
 3. A SEPARATE IRREGATION METER AND BACK-
 FLOW PREVENTER ON THAT LINE IS
 RECOMMENDED.
 4. ALL INTALLATION TO CITY SERVICES MUST
 BE PER CITY STANDARDS. 659-8040
 5. ALL BROKEN SIDEWALKS ALONG THE
 PROPERTY (ALL SIDES) MUST BE REPLACED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI