Plan Review Notes
Plan Review Notes For Permit 02100604
Permit Number 02100604
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-10 00:00:00*********FAILED**************
  
 1. FBC REQUIRES HURRICANE PANELS ON ALL
 OPENINGS CHANGED.PLEASE SUBMIT PRODUCT
 APPROVALS FOR HURRICANE PANELS FOR ALL
 WINDOWS REPLACING AND ADD TO PERMIT
 APPLICATION DESCRIPTION.
 2. NEED DRAWING SHOWING FOOTPRINT OF
 EXTERIOR WALLS OF HOUSE WITH ALL
 WINDOWS NOTED.NUMBER WINDOWS ON
 DRAWING.DESIGNATE LOCATIONS OF ALL
 WINDOWS IN BEDROOMS FOR MEANS OF EGRESS.
 3. PREPARE SCHEDULE SHOWING ANCHORING OF
 HURRICANE PANELS PER FBC 2001.
 4. NEED DESCRIPTION AND DETAILS OF
 REPAIRS FOR SCREEN ROOM.STRUCTURAL?
 TYPE OF MATERIALS USED IN REPLACEMENT.
 SHOW DRAWING OF PORCH.
  
 NOTE:ALL SUBMITTALS MUST BE IN
 DUPLICATE.ONE SET IS ATTACHED TO THE
 PERMIT AND THE OTHER SET IS FOR DEPT.
 FILES.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394