| 2002-11-14 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE A SOIL BEARING TEST REPORT |
| | FROM A SOIL ENGINEER, INDICATING THE |
| | MINIMUM SAFE BEARING VALUE OF THE SOIL. |
| | SEE CITY OF WPB AMENDMENTS TO THE 2001 |
| | FBC SECTION 1804.2.2. |
| | |
| | 3) PLEASE CLARIFY THE "USP" HUG 26 |
| | TRUSS HANGER SPECIFIED ON SHEET S-2. |
| | THERE IS NO CONNECTOR LISTED IN THE USP |
| | CATALOG WITH THIS DESIGNATION. |
| | |
| | 4) THE ROOF SHEATHING NAILING ZONE FOR |
| | THE GABLE AT THE FRONT ENTRY IS ZONE 3. |
| | PLEASE REVISE THE DIAGRAM ON SHEET S-2 |
| | TO INDICATE THIS. |
| | |
| | 5)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - HORIZONTAL STRUCTURAL MULLIONS |
| | - SINGLE OUTSWING DOOR WITH ONE SIDELITE |
| | (THE ONE SUBMITTED IS FOR A DOOR WITH |
| | TWO (2) SIDELITES ONLY AS SHOWN ON THE |
| | APPROVED DRAWINGS. |
| | - SLIDING GLASS DOORS |
| | |
| | 6) THE STORM PANEL INSTALLATION SCHEDULE |
| | CONTAINS ERRORS. PLEASE CORRECT. |
| | |
| | 7) THE ELEVATIONS INDICATE A TRANSOM |
| | WINDOW ABOVE THE (2) SINGLE HUNG WINDOWS |
| | IN THE LIVING ROOM. THIS IS NOT |
| | INDICATED ON THE FLOOR PLAN ON A-1. |
| | PLEASE CLARIFY. |
| | |