Plan Review Notes
Plan Review Notes For Permit 02100591
Permit Number 02100591
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING.
  
 1) SHT A.1 PER TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AND SECTION
 11-4-1-3(10)(A) PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. ALSO SEE SECTION 410.1.
 2) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM FOR NEW
 FIXTURE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377