2002-11-05 00:00:00BUILDING DENIED
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR EXTERIOR WINDOWS
 AND DOOR.
  
 3) PROVIDE ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY FBC CHAPTER 13.
  
 4)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 5)THE LOCATION OF THE ADDITION INDICATED
 ON THE SURVEY DOES MATCH THE PLANS.
 THE PLANS SHOW A 6 FT. SPACE BETWEEN THE
 REAR OF THE EXISTING STRUCTURE AND THE
 ADDITION.
  
 6) MECHANICAL VENTILATION IS REQUIRED TO
 BE INSTALLED IN THE EXISTING BATH WHEN
 WINDOW IS REMOVED. SEE FBC 1203.4.2.
  
 7) THE NAIL SPACING FOR THE ROOF
 SHEATHING IS REQUIRED TO BE 6" O.C. IN
 THE FIELD. PLEASE REVISE. SEE CITY OF
 WPB AMENDMENTS TABLE 2306.1.
  
 8) SPECIFY ATTIC VENTILATION AS REQUIRED
 BY FBC 2309.7.
  
 9) SPECIFY EXTERIOR WALL FINISH.
  
 10) SPECIFY INTERIOR WALL FINISH,
 INSULATION, FURRING, ETC.
  
 11) SPECIFY THE REQUIRED MIN. 12" BELOW
 FINISH GRADE TO THE BOTTOM OF FOOTERS
 AND MIN. 4 INCHES ABOVE FINISH GRADE TO
 FINISH FLOOR. SEE FBC 1804.1.3 AND CITY
 AMENDMENTS 1804.1.7.
  
 12) SPECIFY THE DEPTH OF EMBEDMENT FOR
 THE #5 DOWELS INTO THE EXISTING
 FOUNDATION.
  
 13)INDICATE HOW THE TIE BEAMS OR COLUMNS
 FOR THE ADDITION WILL BE TIED INTO THE
 EXISTING STRUCTURE.
  
 14) SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE 2X10 JOISTS TO THE
 EXISTING STRUCTURE.
  
 15) SPECIFY THE SLOPE OF THE FLAT ROOF.
 A MINIMUM SLOPE OF 1/4" PER FOOT IS
 REQUIRED PER FBC 1508.3.1.
  
 16) THE ELEVATIONS INDICATE THE RAFTERS
 ON TOP OF THE EXISTING TIE BEAM AND THE
 CROSS SECTION APPEARS TO SHOW A 2X10
 LEDGER ATTACHED TO THE SIDE OF THE
 EXISTING TIE BEAM. PLEASE CLARIFY.
  
 17) INDICTE THE CEILING HEIGHT IN THE
 ADDITION.
  
 18) THE PRODUCT APPROVAL FOR THE DOOR
 DOES NOT HAVE THE CORRECT PAGES ONE AND
 TWO (DIFFERENT ACCEPTANCE NUMBERS). THE
 APPROVED DRAWINGS ARE ALSO MISSING.
  
 19) PROVIDE BUCK DETAILS FOR THE WINDOWS
 AND DOOR. INDICATE THE FASTENERS AND
 SPACING.
  
 20) THE PRODUCT APPROVALS FOR THE
 WINDOWS ARE NOT LEGIBLE. THE DRAWINGS DO
 NOT HAVE THE PRODUCT ACCEPTANCE NUMBER
 OR STAMP ON THEM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202