| Notes |
| Date |
Text |
| 2003-10-14 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. PLEASE SEE SOME CIRCUIT | | | #S SEEM TO HAVE BEEN MISPRINTED. | | | A'S-B'S. | | | PLEASE ALSO SEE 700.12E FOR CIRCUITING | | | OF EM/EXT LTS.SEE UNIT 2&4. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|