Plan Review Notes
Plan Review Notes For Permit 02100481
Permit Number 02100481
Review Stop B
Sequence Number 5
Notes
Date Text
2003-03-26 00:00:00THE PLANS SUBMITTED FOR REVISION ARE NOT
 SIGNED, SEALED AND DATED BY THE
 ARCHITECT.FBC 104.2.2.
  
 SHEET A2.THE DOORS ARE NOT PERMITTED
 TO SWING OVER THE PUBLIC RIGHT OF WAY.
 FBC 3203.
  
 THE FOAM TRIM DEPICTED ON SHEETA3 IS
 REQUIRED TO BE NON-COMBUSTIBLE ARE FIRE
 RETARDANT TREATED.SEE FBC F 102.2.7
 AS AMENDED BY THE CITY.
  
 PLEASE PAY THE ADDED PERMIT VALUATION
 FOR THE ADDITIONAL WORK SHOWN AS A
 RATED TENANT SEPARATION WALL AND TOILET
 ROOM.
  
 PLEASE CLEARLY INDICATE THE MOST RECENT
 REVISIONS IN ACCORDANCE WITH GOOD
 ARCHITECTURAL PRACTICE.