2002-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-5 PLEASE SHOW A HORIZONTAL
 RISER DIAGRAM SHOWING ALL NEW BATHROOMS
 AND HOW THEY TIE INTO THE BLDG DRAIN.
 2) SHT A-5 PREVIOUS REVIEW REQUESTED A
 WATER RISER DIAGRAM. PLEASE SUBMIT RISER
 WITH WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 NEAR FIXTURES NOT AT TOP
 OF DROP.
 3) SHOW LOCATION OF WATER FOUNTAINS ON
 FLOOR PLAN AND ON BOTH RISERS. ALSO SEE
 SECTION 410.1, IF WATER COOLERS ARE BE-
 ING USED THEY SHALL BE ARI-1010 COMPLI-
 ANT. SUBMIT MANUF. INFO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377