Plan Review Notes
Plan Review Notes For Permit 02100481
Permit Number 02100481
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-15 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASENOTE, NO SERVICE
 CONDUCTORS FROM GUTTER TO METER, METER
 TO MAINS.215-5
  
 2)NOTE: PLEASE NOTE, ALL MAIN DISC`S ARE
 SHOWN AS 125A WITH LOADS EXCEEDING
 RATINGS OF MAINS? 134,133,149 ETC.
  
  
 3)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. 215-3,230
 -42.
  
 4)NOTE: PLEASE SHOW CIRCUIT #`S ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES.
  
 5)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 SHOW EITHER NEW OR EXISTING EMERGENCY
 LTS/ EXIT LTS. 700-12
  
 6)NOTE: PLEASE SHOW LOCATIONS OF PANELS
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVCE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUETIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372