Plan Review Notes
Plan Review Notes For Permit 02100473
Permit Number 02100473
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-10 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS/480V ARE REQ`D
 TO BE DONE BY AN ENGINEER FBC 104.4.1.3,
 FS 553-79-6, 471.003.
  
  
 2)NOTE: PLEASE NOTE PLANS ARE SHOWING
 A COMPLETE NEW SERVICE. PLEASE CLARIFY
 LOCATION AND OR IF EXISTING SERVICE IS
 BEING REMOVED?
  
 3)NOTE: PLEASE NOTE VOLTAGE ON TRANS-
 -FORMER SHOWN AT 408V?
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS. TABLE 250-122
  
 5)NOTE:PLEASE SHOW GROUNDING FOR TRANS-
 -FORMERS PER 250-50
  
 6)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS
 TO BE ON PLANS AND CORRELATE W/ PANEL
 SCHEDULES.
  
 7)NOTE: PLEASE NOTE MISSING DETAIL FOR
 GROUNDING ELECTRODE SYSTEM.
  
 8)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 PLEASE NOTE 700-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372