| Plan Review Notes For Permit 02100473 |
| Permit Number |
02100473 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-10 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE PLANS/480V ARE REQ`D | | | TO BE DONE BY AN ENGINEER FBC 104.4.1.3, | | | FS 553-79-6, 471.003. | | | | | | | | | 2)NOTE: PLEASE NOTE PLANS ARE SHOWING | | | A COMPLETE NEW SERVICE. PLEASE CLARIFY | | | LOCATION AND OR IF EXISTING SERVICE IS | | | BEING REMOVED? | | | | | | 3)NOTE: PLEASE NOTE VOLTAGE ON TRANS- | | | -FORMER SHOWN AT 408V? | | | | | | 4)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS. TABLE 250-122 | | | | | | 5)NOTE:PLEASE SHOW GROUNDING FOR TRANS- | | | -FORMERS PER 250-50 | | | | | | 6)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS | | | TO BE ON PLANS AND CORRELATE W/ PANEL | | | SCHEDULES. | | | | | | 7)NOTE: PLEASE NOTE MISSING DETAIL FOR | | | GROUNDING ELECTRODE SYSTEM. | | | | | | 8)NOTE: PLEASE SEE FIRE REVIEW COMMENTS, | | | PLEASE NOTE 700-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|