| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | THE PROPOSED ADDITION IS SUBJECT TO | | | IMPACT FEES COLLECTED BY THE COUNTY. | | | THE PERMIT PLANS MUST BE STAMPED BY | | | THAT OFFICE AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-233-5025 FOR | | | MORE INFORMATION. | | | | | | PROVIDE ATTIC VENTILATION IN ACCORDANCE | | | WITH FBC 2309.7. | | | | | | THE PRODUCT NOA 01-0711.03 FOR THE | | | SINGLE HUNG WINDOW IS ILLEGIBLE. | | | PLEASE PROVIDE CLEAR COPIES. | | | | | | SHOW HOW THE HURRICANE MISSILE IMPACT | | | RESISTANCE, (SHUTTERS), WILL BE | | | ACCOMPLISHED. | | | | | | SHOW THE COMPONENT AND CLADDING | | | PRESSURES FOR THE ROOF.SEE FBC | | | 1606.1.7. |
|