2003-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02100425
 ADD: 6901 OKEECHOBEE BLVD
 CONT: D & J CONSTRUCTION
 TEL: (954)689-6405 #204
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) MISSING ORIGINAL PERMIT APPLICATION
 ONLY 1ST RESUB SHEET SUBMITTED.
  
 2) AS INDICATED ON FIRST REVIEW, PERMIT
 FEES ARE TO LOW, PROVIDE A SIGNED COPY
 OF CONTRACT WITH DETAILED TAKE OFF.
  
 3)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 THE PRODUCT TESTING REPORT SUBMITTED IN-
 DICATES IT IS FOR WIND, NOT LARGE MISSLE
 IMPACT RESISTANT.
 W.P.B. STANDARD FOR LARGE MISSLE IMPACT:
 (17) IF THE PRODUCT TESTING REPORTS
 SUBMITTED AT TIME OF PERMIT APPLICATION
 DO NOT REFRENCE THE LARGE MISSLE TESTING
 THEN A SEPERATE PERMIT WILL BE REQUIRED
 FOR THE PROTECTION DEVICE/ ASSEMBLY AND
 NO CERTIFICATE OF OCCUPANCY OR CERTIFI-
 CATE OF COMPLETION SHALL BE ISSUED UNTIL
 INSTILLATION OF GLAZING PROTECTION IS
 COMPLETE. PROVIDE STORM SHUTTER APPROVAL
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 PROVIDE INFORMATION AS WHEN STORM
 SHUTTERS ARE BEING INSTALLED HOW WILL
 CUSTOMERS AND EMPLOYEES EXIT THE BUILD-
 ING. PROVIDE A LIFE SAFETY PLAN FOR THIS
 SENARIO!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412