| 2003-01-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 02100425 |
| | ADD: 6901 OKEECHOBEE BLVD |
| | CONT: D & J CONSTRUCTION |
| | TEL: (954)689-6405 #204 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) MISSING ORIGINAL PERMIT APPLICATION |
| | ONLY 1ST RESUB SHEET SUBMITTED. |
| | |
| | 2) AS INDICATED ON FIRST REVIEW, PERMIT |
| | FEES ARE TO LOW, PROVIDE A SIGNED COPY |
| | OF CONTRACT WITH DETAILED TAKE OFF. |
| | |
| | 3)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | THE PRODUCT TESTING REPORT SUBMITTED IN- |
| | DICATES IT IS FOR WIND, NOT LARGE MISSLE |
| | IMPACT RESISTANT. |
| | W.P.B. STANDARD FOR LARGE MISSLE IMPACT: |
| | (17) IF THE PRODUCT TESTING REPORTS |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | DO NOT REFRENCE THE LARGE MISSLE TESTING |
| | THEN A SEPERATE PERMIT WILL BE REQUIRED |
| | FOR THE PROTECTION DEVICE/ ASSEMBLY AND |
| | NO CERTIFICATE OF OCCUPANCY OR CERTIFI- |
| | CATE OF COMPLETION SHALL BE ISSUED UNTIL |
| | INSTILLATION OF GLAZING PROTECTION IS |
| | COMPLETE. PROVIDE STORM SHUTTER APPROVAL |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING.FBC 1606.1.4. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | PROVIDE INFORMATION AS WHEN STORM |
| | SHUTTERS ARE BEING INSTALLED HOW WILL |
| | CUSTOMERS AND EMPLOYEES EXIT THE BUILD- |
| | ING. PROVIDE A LIFE SAFETY PLAN FOR THIS |
| | SENARIO! |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |