Plan Review Notes
Plan Review Notes For Permit 02100425
Permit Number 02100425
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-10-31 00:00:001) ALL EXITS ARE TO REMAIN CLEAR
 AND ACCESSIBLE DURING CONSTRUCTION.
  
 2) DUST AND SECURITY PARTITIONS ARE NOT
 TO BE CONSTRUCTED OF NON FIRE RATED
 MATERIALS. VISQUEEN AND OTHER NON
 APPROVED MATERIALS SHALL NOT BE USED.
  
 3) NEW SLIDING DOORS AT NEW ENTRANCE TO
 COMPLY WITH THE 2000 LSC, SECTION
 7.2.1.9.1.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD,DUCT AND EXTINGUISHING
 SYSTEMS.
  
 5) PLEASE INDICATE NEW INTERIOR FINISHES
 PLANNED FOR THE LOCATION. PLEASE
 INDICATE WHAT CLASSIFICATION.
  
 6) THE FIRE SPRINKLER SYSTEM SHALL
 REMAIN ON AT ALL TIMES. THE FIRE
 SPRINKLER SYSTEM SHALL NOT BE TURNED
 OFF UNLESS ABSOLUTLELY NECESSARY.
 NOTIFICATION OF FIRE RESCUE IS REQUIRED.
 APPROVED FIRE WATCH ACTIVITIES WILL
 ALSO BE REQUIRED.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER SYSTEM REMODEL.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910