| Plan Review Notes For Permit 02100425 |
| Permit Number |
02100425 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-31 00:00:00 | 1) ALL EXITS ARE TO REMAIN CLEAR | | | AND ACCESSIBLE DURING CONSTRUCTION. | | | | | | 2) DUST AND SECURITY PARTITIONS ARE NOT | | | TO BE CONSTRUCTED OF NON FIRE RATED | | | MATERIALS. VISQUEEN AND OTHER NON | | | APPROVED MATERIALS SHALL NOT BE USED. | | | | | | 3) NEW SLIDING DOORS AT NEW ENTRANCE TO | | | COMPLY WITH THE 2000 LSC, SECTION | | | 7.2.1.9.1. | | | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY NEW HOOD,DUCT AND EXTINGUISHING | | | SYSTEMS. | | | | | | 5) PLEASE INDICATE NEW INTERIOR FINISHES | | | PLANNED FOR THE LOCATION. PLEASE | | | INDICATE WHAT CLASSIFICATION. | | | | | | 6) THE FIRE SPRINKLER SYSTEM SHALL | | | REMAIN ON AT ALL TIMES. THE FIRE | | | SPRINKLER SYSTEM SHALL NOT BE TURNED | | | OFF UNLESS ABSOLUTLELY NECESSARY. | | | NOTIFICATION OF FIRE RESCUE IS REQUIRED. | | | APPROVED FIRE WATCH ACTIVITIES WILL | | | ALSO BE REQUIRED. | | | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FIRE ALARM SYSTEM REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|