| Plan Review Notes For Permit 02100408 |
| Permit Number |
02100408 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-15 00:00:00 | DENIED: | | | | | | PLEASE PROVIDE EQUIPMENT SIZING CALCS | | | (MANUAL J OR SIGNED, SEALED SUMMARY | | | SHEET IN LIEU OF THE COMPLETE SIZING | | | CALCS) AS PER 2001 FBC CHAPTER 13 | | | SECTION 607. | | | | | | PROVIDE CFM DISTRIBUTION. | | | | | | BEDROOMS ARE REQUIRED TO HAVE - | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | PROVIDE INFORMATION ON THE EQUIPMENT | | | TO BE INSTALLED (MAKE, MODEL, BTU'S & | | | SEER OF THE CONDENSER). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|