Plan Review Notes
Plan Review Notes For Permit 02100408
Permit Number 02100408
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-15 00:00:00DENIED:
  
 PLEASE PROVIDE EQUIPMENT SIZING CALCS
 (MANUAL J OR SIGNED, SEALED SUMMARY
 SHEET IN LIEU OF THE COMPLETE SIZING
 CALCS) AS PER 2001 FBC CHAPTER 13
 SECTION 607.
  
 PROVIDE CFM DISTRIBUTION.
  
 BEDROOMS ARE REQUIRED TO HAVE -
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 PROVIDE INFORMATION ON THE EQUIPMENT
 TO BE INSTALLED (MAKE, MODEL, BTU'S &
 SEER OF THE CONDENSER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved