Plan Review Notes
Plan Review Notes For Permit 02100398
Permit Number 02100398
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-10-08 00:00:001) PLANS DO NOT SHOW THE LOCATIONS OF
 EXISTING OR NEW EXIT SIGNS. PLEASE SHOW
 HOW OCCUPANTS WILL EXIT THE SPACE.
  
 2) IS THERE EXISTING EMERGENCY LIGHTING
 AND WHAT ARE THE LOCATIONS?
  
 3) THE PLAN DOES NOT INDICATE THE TYPE
 OF INTERIOR FINISH BEING USED. PLEASE
 INDICATE THE TYPE OF INTERIOR FINISH.
  
 4) IS THERE A FIRE SPRINKLER AND ALARM
 SYSTEM IN THIS BUILDING AND IF SO, HOW
 DOES THIS WORK IMPACT THOSE SYSTEMS?
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 659-8096, EXT. 8497
 835-2910