| Plan Review Notes For Permit 02100398 |
| Permit Number |
02100398 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-08 00:00:00 | 1) PLANS DO NOT SHOW THE LOCATIONS OF | | | EXISTING OR NEW EXIT SIGNS. PLEASE SHOW | | | HOW OCCUPANTS WILL EXIT THE SPACE. | | | | | | 2) IS THERE EXISTING EMERGENCY LIGHTING | | | AND WHAT ARE THE LOCATIONS? | | | | | | 3) THE PLAN DOES NOT INDICATE THE TYPE | | | OF INTERIOR FINISH BEING USED. PLEASE | | | INDICATE THE TYPE OF INTERIOR FINISH. | | | | | | 4) IS THERE A FIRE SPRINKLER AND ALARM | | | SYSTEM IN THIS BUILDING AND IF SO, HOW | | | DOES THIS WORK IMPACT THOSE SYSTEMS? | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | 659-8096, EXT. 8497 | | | 835-2910 |
|