| 2002-10-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT A-1 NEW RESTROOM,(W-108A), ADJAC- |
| | ENT TO COFFEE ROOM SHALL COMPLY WITH SEC |
| | 11-4.22 PER 11-4.1.3(11). MINIMUM WIDTH |
| | REQUIRED IS 5'3", AND 5'0" IS SHOWN. |
| | 2) SHT A-1 WOMENS, (W-114), HDCP STALL |
| | MINIMUM WIDTH IS 5'3" AND 5'0" IS SHOWN. |
| | 3) SHT A-1 DOORS SHALL NOT OPEN INTO THE |
| | CLEAR FLOOR SPACE OR UNOBSTRUCTED 5' |
| | TURNING RADIUS IN ROOMS W-125 & W-126. |
| | 4) SHT A-2 PLUMBING NOTES, AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE REFEREN- |
| | CE. WATER HAMMER ARRESTORS ONLY REQUIRED |
| | BY SEC. 604.9 SHALL BE INSTALLED. |
| | 5) SHT A-2 SANITARY RISER DIAGRAM, FLOOR |
| | DRAINS IN MEN'S AND WOMEN'S SHOWER AREA |
| | ARE NOT VENTED. FLOOR DRAIN SHOWN IN |
| | MEN'S REST ROOM W-126 IS NOT SHOWN ON |
| | THE RISER DIAGRAM. |
| | 6) WATER RISER DIAGRAM IS REQUIRED. IF |
| | WATER HAMMER ARRESTORS ARE SHOWN, THEY |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT OVERHEAD IN CEIL- |
| | ING. |
| | 7) SHT A-4 COFFEE ROOM SINK SHALL COMPLY |
| | WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE |
| | SHOW ON DETAIL. |
| | 8) TABLE 403.1 REQUIRES DRINKING FOUNT- |
| | AINS AND A SERVICE SINK. PLEASE INDICATE |
| | IF THESE FIXTURES ARE PROVIDED. |
| | |
| | REVIEW BY KEN STEVENS |