| Plan Review Notes For Permit 02100324 |
| Permit Number |
02100324 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-29 00:00:00 | PROVISO: | | | | | | FIRE DAMPERS SHALL COMPLY WITH THE | | | REQUIREMENTS OF UL 555.PROVIDE | | | MANUFACUTURER SUBMITTAL AND | | | INSTALLATION INSTRUCTIONS ON THE | | | JOBSITE AT THE TIME OF INSPECTION. | | | 2001 FBC(M) 607.1.1 & 607.6. | | | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM.2001 FBC(M) | | | 602.1.1. | | | | | | PLANS DO NOT INDICATE DUCT SMOKE | | | DETECTORS.AS PER 2001 FBC(M) 606.2.1, | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY AIR SYSTEMS WITH A DESIGN | | | CAPACITY GREATER THAN 2,000 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|