| Plan Review Notes For Permit 02100323 |
| Permit Number |
02100323 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | FBC-2001 FUEL GAS SEC 401.8 THRU 402.5.2 | | | AND TABLES 402(1) THRU 402(34). | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS APPENDIX A - USE OF | | | CAPACITY TABLES (A)(3). | | | 5. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 GAS CODE SEC. 402.2. IF | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|