2002-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS SEC 401.8 THRU 402.5.2
 AND TABLES 402(1) THRU 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS APPENDIX A - USE OF
 CAPACITY TABLES (A)(3).
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE SEC. 402.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS