| Plan Review Notes For Permit 02100300 |
| Permit Number |
02100300 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-06-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE NECESSARY CHANGES | | | TO THE PLANS FOR CODE COMPLIANCE. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} THE EQ GROUND FROM THE METER TO THE | | | FIRST MEANS IS CREATING A PARALLEL PATH | | | TO GROUND AND IS IN VIOLATION OF | | | 250-24. REMOVE IT . | | | | | | 5} SEE REVIEWED PLAN FOR AREAS THAT DO | | | NOT COMPLY WITH 210-52(A)(1),210-52(C)& | | | 210-52(D). | | | | | | 6} THE REVISION SHEET INDICATES THE | | | AREAS OF CHANGE WOULD BE CLOUDED,THERE | | | ARE NO CLOUDS ON SHEET A-11,PLEASE | | | CLOUD SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|