2003-07-14 00:00:00PROVISO:
  
 AIR HANDLING UNIT #2 -
 AIR HANDLING UNITS INSTALLED IN ATTICS
 SHALL COMPLY WITH THE FOLLOWING AS PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 6 SEC
 610.1.ABC.3.5.2 & 2001 FBC(M) 306.3:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FEET OF AN ATTIC ACCESS
  
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT THE UNIT DOWN WHEN THE
 CONDENSATION DRAIN IS WORKING PROPERLY.
  
 3. THE ATTIC ACCESS OPENING SHALL BE
 SUFFICIENT SIZE TO REPLACE THE AHU, NOT
 LESS THAN 20" X 30".
  
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE HOME
 OWNER THAT THE AHU IS LOCATED IN THE
 ATTIC.
  