| 2002-11-15 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 104.2.1.2BOUNDARY SURVEY. |
| | SUBMIT TWO COPIES OF A SIGNED, SEALED |
| | AND DATED SURVEY DRAWING. |
| | |
| | 4) FBC 1606.1.1VERTICAL WALL REINF. |
| | SPACING (REF: SBCCI STANDARD, SSTD-10, |
| | TABLE 205C).WHAT IS THE BASIS OF THE |
| | LOADS IN THE UPLIFT TABLE ON SHEET A-1? |
| | SHEET A-6, DETAIL 1 - TYPICAL WALL |
| | SECTION, SPECIFIES #5 VERTICAL REINF. IN |
| | FILLED CELLS.SSTD 10, TABLE 205C |
| | REQUIRES 1#5 AT 6FT MAX. SPACING FOR 8" |
| | MASONRY WITH A CEILING HEIGHT OF 10 FT. |
| | SHEET A-1, FOUNDATION PLAN, SHOWS |
| | GREATER SPACING, UPTO 9'-10".ALTHOUGH |
| | SOME DOUBLE FILLED CELLS ARE SHOWN, |
| | AMEND THE PLANS PER TABLE 205C OR |
| | JUSTIFY DEVIATION FROMTHE PRESCRIPTIVE |
| | STANDARD. |
| | |
| | 5) THE SUBMITTED THERMA-TRU CORP. DOUBLE |
| | OUTSWING OPAQUE INSULATED STEEL DOOR, |
| | PRODUCT APPROVAL NOA# 02.0805.03 IS |
| | ACCOMPANIED BY DRAWINGS WHICH DO NOT |
| | CARRY THE MIAMI-DADE COUNTY PRODUCT |
| | CONTROL RENEWAL STAMP BEARING THE ABOVE |
| | NOA NUMBER AND EXPIRATIONDATE.ALSO, |
| | THE COPIES ARE POOR QUALITY.SUBMIT |
| | LEGIBLE COPIES OF THE APPROPRIATE |
| | DRAWINGS BEARING THE REQUIRED STAMP. |
| | |
| | 6) FOR YOUR INFORMATION, SHEET A-4 - |
| | LEFT AND RIGHT ELEVATIONS DO NOT SHOW |
| | THE CORRECT PROFILE FOR THE ROOF OVER |
| | THE FOYER. |
| | |
| | 7) FBC 1005.4 EGRESS WINDOWS.THE FACT |
| | THAT THE SPECIFIED EGRESS WINDOW SIZES |
| | DO CONFORM TO CODE, IS NOTED.FOR YOUR |
| | INFORMATION, THE NOTE ON SHEET A-8 WOULD |
| | NOT ENSURE COMPLIANCE WITH FBC 1005.4.4 |
| | IT STATES THAT THE MINIMUM TOTAL GLASS |
| | AREA FOR A GROUND FLOOR EGRESS WINDOW IS |
| | 5.0 SQ FT AND THAT THE NET CLEAR OPENING |
| | SHALL NOT BE LESS THAN 4 SQ FT.THE |
| | NOTE SHOULD REQUIRE A MINIMUM OF 5 SQ FT |
| | NET CLEAR OPENING FOR THE GROUND FLOOR |
| | EGRESS WINDOWS (REF: RBC 1005.4.4) |
| | |
| | 8) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |