Plan Review Notes
Plan Review Notes For Permit 02100300
Permit Number 02100300
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-24 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW AIC RATINGS FOR
 MAINS/ PANELS/BRKRS REQ`D PER 110-9/
 215-5.
  
 2)NOTE: PLEASE NOTE MISSING SD IN GUEST
 BEDROOM. PLEASE SEE NFPA-72 8-1.4.1.6
  
 3)NOTE: PLEASE SEE SERVICE CONDUCTORS,
 PLEASE NOTE AN EQUIPMENT GROUNDING
 CONDUCTOR IS NOT INSTALLED BETWEEN
 METER AND MAIN DISC. 250-24. PLEASE
 ALSO SEE WIRE SIZES. SOME SHOWN MUCH
 LARGER(MISPRINT) 6/0 AND 10/0`S ??
 PLEASE NOTE THAT THESE ARE NOT WIRE
 SIZES THAT CORRELATE WITH NEC. 310-16
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372