| 2002-11-08 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | --PROVISO-- |
| | SHEET 2 OF THE INTEGRA ROOF TILE PRODUCT |
| | APPROVAL NOA# 01-0703.04 IS MISSING. |
| | THE SUBMITTED SHEET 2 IS FROM A |
| | DIFFERENT PRODUCT APPROVAL (THE SHEET IS |
| | HEADED: NOA# 01-0509.09, TAMKO ROOFING |
| | PRODUCTS, INC.).SUBMIT TWO COPIES OF A |
| | COMPLETE PRODUCT APPROVAL. |
| | |
| | --PROVISO-- |
| | DRAWING SHEETS 1, 3 AND 5 OF THE PGT |
| | SERIES SH-400 SINGLE HUNG WINDOW PRODUCT |
| | APPROVAL NOA# 01-0516.10 INCLUDE TABLES |
| | WHICH ARE ILLEGIBLE DUE TO POOR COPY |
| | QUALITY.SUBMIT TWO LEGIBLE COPIES. |
| | |
| | --PROVISO-- |
| | DRAWING SHEETS 2 OF THE PGT SLIDING |
| | GLASS DOOR PRODUCT APPROVAL |
| | NOA# 00-0301.03 IS MISSING.SUBMIT TWO |
| | COPIES OF A COMPLETE PRODUCT APPROVAL. |
| | |
| | --PROVISO-- |
| | THE SIZES OF THE FIXED WINDOWS IN THE |
| | FRONT ELEVATION, REAR ELEVATION AND LEFT |
| | ELEVATION ARE OUTSIDE THE SCOPE OF THE |
| | SUBMITTED PGT FIXED WINDOW PRODUCT |
| | APPROVAL NOA# 99-1110.04.SUBMIT AN |
| | APPROPRIATE PRODUCT APPROVAL, WHICH |
| | SHALL EITHER INCLUDE MULLIONS OR BE |
| | ACCOMPANIED BY A SEPARATE MULLION |
| | PRODUCT APPROVAL FOR THE MULLED WINDOW |
| | CONFIGURATIONS. |