| 2002-11-13 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | --BEFORE PERMIT-- |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | --BEFORE PERMIT-- |
| | THE PROPOSED WORK WILL INCREASE FLOOR |
| | AREA. IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | --PROVISO-- |
| | FBC 3401.7.1.3DUE TO THE INCREASED FLR |
| | AREA, THE RELOCATED STORE FRONT SHALL |
| | CONFORM TO CURRENT CODE REQUIREMENTS. |
| | FBC 1012.1THE PLANS DO NOT STATE THE |
| | DOOR HARDWARE TYPE OR THE OCCUPANCY OF |
| | THE SPACE.THEREFOR, THE DOORS ARE |
| | ASSUMED TO BE EGRESS DOORS AND SHALL |
| | ONLY BE PERMITTED TO HAVE LOCKS/LATCHES |
| | WHICH ARE OPENABLE, USING ONE HAND, |
| | WITHOUT THE USE OF A KEY, TOOL OR |
| | SPECIAL KNOWLEDGE. |
| | |
| | --PROVISO-- |
| | THE HEAD FASTENING ARRANGEMENT FOR THE |
| | METAL FLANGE STUD SHALL BE EQUIVALENT TO |
| | OR BETTER THAN THE EXISTING FASTENING |
| | ARRANGEMENT AT THE CURRENT LOCATION. |
| | ALTERNATIVELY, STATE THE WIND PRESSURES |
| | ON THE PLANS FOR VERIFICATION OF THE |
| | PROPOSED FASTENINGS. |