Plan Review Notes
Plan Review Notes For Permit 02100090
Permit Number 02100090
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-13 00:00:00TRUSSES DENIED
  
 1) THE TRUSS DRAWINGS ARE DESIGNED FOR
 A 110 MPH WINDLOAD THE CITY OF WPB IS
 LOCATED IN A 140 MPH WIND ZONE. SEE FBC
 1606 AND ASCE 7-98.
  
 2) THE DESIGNER OF RECORD FOR THE
 STRUCTURE IS REQUIRED TO REVIEW AND
 APPROVE THE TRUSS DRAWINGS AND LAYOUT.
  
 3) THE TRUSS ENGINEER'S WET SIGNATURE IS
 REQUIRED ON ALL DOCUMENTS SUBMITTED FOR
 PUBLIC RECORD. SEE 61G15-23.002 FAC.
 A SIGNATURE STAMP IS NOT ACCEPTABLE.
  
 4) THE TRUSS PACKAGES FOR ONE AND TWO
 FAMILY DWELLINGS ARE NOT REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. THEY ARE
 REQUIRED TO BE GIVEN TO THE BUILDING
 INSPECTOR TO REVIEW AT TIME OF TRUSS
 INSPECTION AND HE WILL BRING IN THE
 SIGNED AND SEALED DRAWINGS TO BE FILED
 WITH THE APPROVED PLANS FOR PUBLIC
 RECORD.