2002-11-01 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 SPECIFY THE DESIGN CRITERIA ON THE PLANS
 FOR THE STRUCTURAL REPAIRS. REPAIRS
 SHALL COMPLY WITH THE 2001 FLORIDA
 BUILDING CODE. SEE FBC 3401.7.2.4 AND
 3401.7.2.5.
  
 3) REVISE WINDOW AND DOOR BUCK DETAILS
 TO COMPLY WITH FBC SEC.1707.4.4.2. BUCKS
 1-1/2" OR GREATER IN THICKNESS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF
 WIDOW AND DOOR FRAMES.
  
 4) CLARIFY THE "C" TRUSS CONNECTOR
 SPECIFIED ON A2. IS THIS A "USP", USC
 UPLIFT STRAP CONNECTOR? DID YOU INTEND
 TO SPECIFY (8) 16D NAILS, RATHER THAN
 81- 16D NAILS.
  
 5) THE SITE SPECIFIC PRODUCT APPROVALS
 SUBMITTED ARE NOT ACCEPTABLE. THEY DO
 NOT REFERENCE THE 2001 FBC, THEY ARE NOT
 SIGNED, SEALED AND DATED BY THE ENGINEER
 FOR THE PRODUCT AND THEY MUST BE SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD OF THE STRUCTURE. TWO (2) FORMS
 ARE REQUIRED FOR EACH PRODUCT.
  
 6) ONLY ONE COPY OF THE PRODUCT APPROVAL
 FOR THE SINGLE HUNG DUAL ACTION WINDOW
 WAS SUBMITTED, TWO (2) COPIES ARE
 REQUIRED.
  
 7) THE PRODUCT APPROVALS SUBMITTED FOR
 THE SLIDING GLASS DOORS DO NOT APPLY TO
 TWO PANEL DOORS. MOST OF THE INFORMATION
 ON THE DRAWINGS IS ILLEGIBLE. PLEASE
 SUBMIT (2) CLEAR COPIES OF THE
 APPROPRIATE PRODUCT APPROVALS.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR STRUCTURAL WINDOW MULLIONS
  
 9) IMPACT PROTECTION IS REQUIRED FOR ALL
 GLAZED EXTERIOR OPENINGS THAT ARE BEING
 REPLACED PER FBC 1606.1.4.
 PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 10) THE CITY BUILDING INSPECTOR MAY
 REQUEST ADDITIONAL INFORMATION OR
 ENGINEERING AS THE WORK PROGRESSES.
  