| 2002-11-01 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | SPECIFY THE DESIGN CRITERIA ON THE PLANS |
| | FOR THE STRUCTURAL REPAIRS. REPAIRS |
| | SHALL COMPLY WITH THE 2001 FLORIDA |
| | BUILDING CODE. SEE FBC 3401.7.2.4 AND |
| | 3401.7.2.5. |
| | |
| | 3) REVISE WINDOW AND DOOR BUCK DETAILS |
| | TO COMPLY WITH FBC SEC.1707.4.4.2. BUCKS |
| | 1-1/2" OR GREATER IN THICKNESS SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF |
| | WIDOW AND DOOR FRAMES. |
| | |
| | 4) CLARIFY THE "C" TRUSS CONNECTOR |
| | SPECIFIED ON A2. IS THIS A "USP", USC |
| | UPLIFT STRAP CONNECTOR? DID YOU INTEND |
| | TO SPECIFY (8) 16D NAILS, RATHER THAN |
| | 81- 16D NAILS. |
| | |
| | 5) THE SITE SPECIFIC PRODUCT APPROVALS |
| | SUBMITTED ARE NOT ACCEPTABLE. THEY DO |
| | NOT REFERENCE THE 2001 FBC, THEY ARE NOT |
| | SIGNED, SEALED AND DATED BY THE ENGINEER |
| | FOR THE PRODUCT AND THEY MUST BE SIGNED, |
| | SEALED AND DATED BY THE DESIGNER OF |
| | RECORD OF THE STRUCTURE. TWO (2) FORMS |
| | ARE REQUIRED FOR EACH PRODUCT. |
| | |
| | 6) ONLY ONE COPY OF THE PRODUCT APPROVAL |
| | FOR THE SINGLE HUNG DUAL ACTION WINDOW |
| | WAS SUBMITTED, TWO (2) COPIES ARE |
| | REQUIRED. |
| | |
| | 7) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE SLIDING GLASS DOORS DO NOT APPLY TO |
| | TWO PANEL DOORS. MOST OF THE INFORMATION |
| | ON THE DRAWINGS IS ILLEGIBLE. PLEASE |
| | SUBMIT (2) CLEAR COPIES OF THE |
| | APPROPRIATE PRODUCT APPROVALS. |
| | |
| | 8)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR STRUCTURAL WINDOW MULLIONS |
| | |
| | 9) IMPACT PROTECTION IS REQUIRED FOR ALL |
| | GLAZED EXTERIOR OPENINGS THAT ARE BEING |
| | REPLACED PER FBC 1606.1.4. |
| | PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 10) THE CITY BUILDING INSPECTOR MAY |
| | REQUEST ADDITIONAL INFORMATION OR |
| | ENGINEERING AS THE WORK PROGRESSES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |